Starting Up Your Boilers (by Combustion Safety)

We recently saw an excellent article on “Starting Up Your Boilers?” written by Combustion Safety. With their permission, this article has been posted on our website. Whether you have a boiler you intend to be starting soon because of the change of seasons, or another piece of gas fired equipment such as a dryer or furnace, this article is well worth reading. 

This could be the start of another productive season out of your boilers or their destruction, thousands of dollars in repair costs, or even explosion and death. Handling a seasonal start-up correctly can make all the difference in the world. Some amount of carnage related to boiler start-ups seems to occur somewhere every year. This kind of tragedy is absolutely unnecessary and can be avoided if you just carefully read and communicate the tips that follow. These lessons focus on your boiler's fuel and flame safety systems. If learned well you will have a better chance of staying alive during the first few seconds of the light-off process and the rest of the season.

Here are three fuel-system start-up lessons you can't afford to ignore.

1.Your firebox may be full of fuel! One false move could make for a disaster!

Never, ever, walk up to a boiler or any piece of combustion equipment that has been down for a long period of time, especially a heating boiler that is been down all summer, and just hit the start button. A firebox concentration of only 4.3 % natural gas can create a flammable mixture. Some valves can leak through 1 cubic foot of gas per hour or more. Consider the consequences of a valve leaking through at this rate for several months while your boiler is laid up. Making a wrong move here and trying to start-up in this condition could make for a catastrophic explosion.

There are several shut-off valves in your gas train, which are supposed to be tight. These exist to keep gas out of the firing chamber when the unit is off. Our experience is that 60% of lubricated plug valves leak through when in the closed position. In addition, automatic safety shut-off and solenoid valves also leak through when closed.

By design, manual lubricated plug valves are nothing more than two pieces of metal with an air gap between them. A tight shut-off seal only occurs when a special sealant is present. This sealant lubricates and seals the surfaces. If this sealant does not exist the valve body will tend to corrode and lock into a fixed position with the plug. The end result is that you will not be able to move the valve from its fixed position no matter how hard you try. If you discover a bad gas leak or a fire breaks out, you will not be able to budge the valve. Most sites do not understand the concept of how these valves work and do not have the proper sealant or injection equipment.

The process of tightness testing automatic safety shut-off or pilot valves should be completed at least annually. The objective is to measure the rate at which bubbles flow downstream of a supposedly closed valve. This process requires training for it to be performed safely.

If you can not verify that you do not have a hazardous situation on your hands, you should treat the situation as if it is. Carefully insert a flammability meter probe into the firebox and measure the LEL (lower explosive limit) of the firebox atmosphere. If you are even close to the LEL make sure you safely purge without any possibility of a spark before proceeding.

2. Your safety interlock protection may not be working!!!

Time and inactivity are two factors that you must take into consideration during start-up. Inactivity means parts have not moved in a long time. The passage of time invites changes in environmental factors such as moisture and temperature. These two issues alone can make for unwelcome surprises. When parts cool off they come closer to the dew point temperature of the surrounding ambient air, which means moisture will condense on a surface. If that surface is the electrical contact of a switch or a vertical piece of vent pipe, corrosion can occur. Corrosion of components can mean the flaking off of rust that can create wedges between valve seating surfaces. It can also mean switch components get stuck in position due to corrosion or even cause switch contacts to no longer make and break reliably.

Cooled off boiler components and summer breezes will also create a more comfortable living environment for insects and birds. We regularly find clogged vent line terminations. Start-up is the right time to look for and correct these items.

We find very few sites doing regular interlock and safety control testing. In most states, lack of regular testing is against the law. It is especially foolish to not test safeties and interlocks in the case of a cold start-up after a down period.

Boiler safety interlocks that require regular testing include the following:

High and low gas pressure switches
Low water cut-offs
High steam pressure switch cut-offs
Flame scanners
Air flow proving switches
Valve proof of closure switches
Low fire start switches

Interlock testing can and should only be done once you are sure the firebox does not contain a flammable mixture. Make sure that whoever does this testing is trained and experienced.

3. Fire In The Hole! (lighting off, what to look for and even where to stand). Pre-Start Walk Around Is A Must!

Make sure that you have a walk down procedure prior to starting up that trains people to look for obvious problems. For example, purge fans are supposed to move fresh air through the firebox in case gas valves have leaked through. If the fans are dirty or have the Sunday newspaper stuck to the air intake all bets are off. In these cases the purge may not happen properly.Likewise, if the high and low gas pressure switches, air switches, or purge timer are set incorrectly you will have lost their ability to protect you and your equipment.

After a thorough walk down remember there are good and bad places to stand during a light-off. One should never stand in front of a burner or any bolted connection like a flue stack. Likewise, some boilers have relief panels built in, which will come apart and off in the case of a firebox explosion. In the case of firetube boilers for example, it is usually best to stand to the side.

There have also been a number of people who have lost their vision looking into sight view ports during light-offs. This is a place to look only with eye protection, and never, ever during a light-off. Always move the view port sight shield, if one exists, and test for hot firebox gasses first before putting your eyes and head in harms way.

When the pilot and main flame are lit you need to immediately look for items such as the quality of the flame and the gas pressure stability entering the burner. A good flame is full and complete along the burner ring. It has movement and is blue with yellow and/or orange tips. If your flame is unstable (going on and off in places), lacks movement, is bright orange or yellow, and/or you see soot coming out of the stack you have major problems. These conditions occur because your air-fuel mixture is too rich. If you shut the unit down in this condition do not try to restart again without allowing a cool down period and the fuel rich atmosphere to dissipate.

Remember, flame scanners and flame detection equipment are not designed to distinguish between good flames and bad flames. This has to be done by a trained human eye.

Once you work through a process for walking down the system and know what to look for, it should become part of a well-documented start-up/shut down procedure. You should include digital pictures of the control panels including close ups of the buttons and labels. Everything should be explained in clear and simple terms that anyone operating the equipment understands.

Conclusion

The issues discussed above are not all-inclusive but make for a great beginning. Many articles have been done in the past that consider steam and water side related start-up issues. We find too many sites do not consider basic fuel and combustion system issues until it is too late. If you want more detail regarding interlocks, testing, and good practices consider the ASME (American Society for Mechanical Engineers) CSD-1 standard. It provides important safety information regarding controls and safety devices for automatically fired boilers between 400,000 and 12,500,000 btuh input. This code has been adopted as law in most states. For larger equipment, NFPA 85 (National Fire Protection Association) is a good reference. Remember, start-up is the most dangerous few minutes in the life of each boiler and operator. Implementing the lessons provided here can make for a time to enjoy the wonders of fall, instead of creating a time for grieving.

This article with pictures is available for download from our website.

3130 South Tech Blvd.
Miamisburg, OH 45342
(937) 886-0000
email
IMPAIRMENTS
(937) 4-IMPAIR

 

 


Strategic Partner for Infrared  

Inc. Magazine ranks Predictive Service as the 523rd fastest growing company in America!This & other Press Releases


Strategic alliance with CEC Combustion Services Group  

Click here to see John Puskar's newest article "Boiler Safety Intuition"


Effective Handling of Fire Protection System Impairments
Clients Call (937) 4-IMPAIR

more...

Seasonal Maintenance Tips
more...